Inrush current limiter for DIN rail mounting. Limits the starting current of electronic ballasts and LED drivers to 33.9 A for 300 ms, an acceptable value for circuit protection.
Module for mounting on 35 mm DIN rail in accordance with DIN 50022, space required: 2 HP Connection terminals 0.5-6 Peak current limit: 48 A (± 6%) RMS current limit: 33.9 A (± 6%) Max. capacitive load: 6000 µF Nominal AC voltage: 230 V AC Nominal AC current: 16 A Limiting speeds: 3 cycles / minute Automatic cutout: 13 A / 16 A Internal safety: Temperature fuse against overload